QUESTIONS WITH 100% RATED CORRECT ANSWERS | GRADE A+
Terms in this set (176)
What is a purpose of a control Control Flow to water based fire protection system
valve
The gauge on the quick opening the same pressure
device shall indicate as
compared to the
gauge on the system side of the
dry pipe valve?
What type of test shall be provided Valve status test
when a valve is returned to
service to determine
that the valve is open?
A pipe and its appurtenances on private property/ Pipe between
What is a fire service main?
a source of water and the base of the system riser
Name the system that utilizes a Orifice Plate Proportioning
plate
through which a passes a specific
amount of foam concentrate at a
specific pressure.
During an inspection, which of the Corrosion
following would be identified as a
sprinkler which shall be
replaced?
What are the inspection Periodic inspection is not required
requirements for hangers and
seismic braces installed in
concealed spaces?
Gauges shall be replaced every yrs 5/5
or
tested everyyrs by comparison
with a
calibrated gauge
, Where air pressure supervision is Monthly
connected to a constantly attended
location gauges shall be inspected
________________________?
Sprinklers installed in areas that Shall/ Inspected
are
inaccessible for safety
consideration, due to process
operations ____ be___
during
each scheduled shutdown?
What type of valve is Pressure reducing valve
designed for the purpose of
reducing downstream water
pressure under both residual
and static conditions
PIV and OS&Y shall be backed a 1/4
__________ turn from the fully
open position to prevent
jamming.
Gauges not accurate to within 3
_______ percent of the full
scale shall be
recalibrated or replaced?
When there is a_ percent reduction 10
in
full flow pressure, when compared
to
original acceptance test, the cause
of the reduction shall be identified
and corrected.
An informational sign shall be System Control Riser
placed at the
___ supplying the antifreeze loop,
dry
system, pre action system, or
auxiliary systems control
valve.
Information signs should indicate Location if the area served by system, the presence and location