Exam. Newest 2025-2026. Questions
with Correct Verified Answers. Graded A
Alarm Signal Deactivation – ANS if an alarm signal is deactivated, both the
audible and visible appliances *shall cease simultaneously
-means for allowing deactivation shall be key operated, located in a locked
cabinet
-if deactivated, the visual indicator of the device/zone in alarm shall remain
lit
Cabling listing for Fire Alarm use - ANSconductors must be solid or
stranded copper (can NEVER be made of aluminum)
single conductors are permitted to be no smaller than #18 AWG
multiple conductor cables may be as small as #26 AWG
Carbon Monoxide Alarms - ANSintended to be either stand-alone or
interconnected
on exam, stand alone only = False
1
, Central Station service - ANSoften for higher-risk, high-dollar applications,
or where an insurance carrier requires it as a condition of being insured
prime contractor is involved
often called certificated systems due to a certificate or placard w/in 3 feet or
the FACU
Class A - ANSPathway includes a redundant path, operates on both sides
of a single open, and conditions that affect the intended operation of the
path are annunciated
Control Panel Mounting Location - ANS**keep 36 inches IN FRONT of all
control panels clear
**always install equipment with environmental restrictions in mind: no
electronic equipment can be installed where temp. dips below 32 degrees F
or above 120 degrees F
Control Panels/Units - ANSreferred to as the Fire Alarm Control Unit
(FACU)
"brains" of any fire alarm system
Delayed Egress Locking Arrangement - ANSpush until alarm sounds
2