Testing Test 2025-2026. Questions
with Correct Verified Answers. Graded
A
According to NFPA 72 following the initial sensitivity test within one year of
installation, how many smoke detectors must be sensitivity tested within the
next two years? - ANS 100%
All supervising station alarm systems transmission equipment shall report
initiating device activation within how long? - ANS90 Seconds
Area of refuge two-way communication systems are required to be tested
in which of the following three ways - ANSVerify Receipt of visual and
audible signal at the transmitting and receiving unit, respectively
Define ADS - ANSAcoustically Distinguishable Space
Define Shall - ANSIndicates a mandatory requirement
Deinfe Should - ANSIndicates a recommendation or that which is advised
but not required
1
, Fire alarm systems that are not monitored for alarm supervisory and trouble
signals shall have their lamps and LED's visually inspected at what
frequency? - ANSquarterly
How are rate of rise heat detectors tested? - ANSHeat gun or something
similar
How do you test a non restorable heat detector? - ANSTest the continuity
of the heat detector
How is the alarm switch of a fire extinguishing system or supression system
tested? - ANSOperating the alarm switch electrically or mechanically
annually, and verifying receipt of the alarm signal at the fire alar control
unit.
How many years after the initial installation shall all fixed temperature non
restorable line type detectors be replaced or have 2 per 100 laboratory
tested? - ANS20 Years
How often are digital alarm communicator transmitters required to be
inspected? - ANSAnnually
How often are fire alarm devices to be cleaned? - ANSAnnually
How often are video image smoke and fire detectors required to be
inspected? - ANSAnnually
2