Answers
Save
Terms in this set (100)
The ASSE 6040 Standard maintain
applies to individuals who
_______________ medical gas
and vacuum systems.
A install
B perform inspections of
new installations
C maintain
D verify
At sea level the 64.7 psia
atmospheric pressure is
14.7 psia. What is the
absolute pressure of a 50
psig (gauge pressure)
system at sea level?
A 64.7 psia
B 50 psia
C 34.7 psia
D 60 psia
,Medical Gas Maintenance Personnel
_______________________________
shall be able to describe
how to find and
implement manufacturer
specific maintenance
requirements for the
medical gas and vacuum
system components per
ASSE 6000 Annex D and
CGA E.10.
A Supplier or Distributor
B Maintenance Personnel
C Authority having
jurisdiction
D Verifier or Inspector
Medical Gas Maintenance All of the above
Personnel shall be able to
identify and describe the
hazards resulting from
improper maintenance of
medical gas and vacuum
systems, including:
A Flow
B Cross Connections
C Contaminants
D All of the above
,ASSE 6000 daily checks of Pressure Dew Point Temperature
bulk liquid systems include
all of the following with
the exception of
______________.
A Primary and Reserve (if
equipped) Tank Contents
B Pressure Dew Point
Temperature
C Leaks or Unusual Icing
D Proper pressure
maintained
Per ASSE 6000 Annex D Daily
typical maintenance
procedures include
_______________ checks of the
Medical Air Moisture
removal system (after
cooler, dryer drain,
receiver drain, sight glass,
etc.).
A Daily
B Weekly
C Monthly
D Annually
Per ASSE 6000 Annex D Both A & B
the Medical Air __________ is
typically checked daily.
A Dew Point Monitor
B Carbon Monoxide
Monitor
C Filter Condition
D Both A & B
E All of the above
, Typical monthly checks, Emergency Instructions
per ASSE 6000 Annex D,
of area alarms include all
of the following except :
A Audible Signal
B Visual Signals
C Emergency Instructions
D Gauge Pressure Read
Outs
Per ASSE 6000 Annex D, Quarterly
the medical air
compressor intake
location and filter
condition should be
checked _______________.
A Daily
B Weekly
C Quarterly
D Annually
Minimum Maintenance All critical care outlets & inlets
Schedule, per ASSE 6000
Annex D, should include
annual checking of
________________ for Flow,
Pressure/Vacuum,
Damage, and Wear.
A All outlets & inlets
B All critical care outlets &
inlets
C 50% of all critical care
outlets
D Annual testing of outlets
& inlets is not
recommended