CWMS) EXAM QUESTIONS WITH 100% VERIFIED
ANSWERS!!
NFPA 1141 - answer -Standard for Fire Protection Infrastructure for Land
Development in Wildland, Rural, and Suburban Areas (2017).
AHJ - answer -Authority Having Jurisdiction.
Windows and openings materials - answer -The structure assessment shall
document the materials used in windows and other openings in vertical surfaces.
Ventilation openings - answer -The structure assessment shall document the
location, size, and screening of ventilation openings.
Accessory structures - answer -The structure assessment shall document all
attached accessory structures as part of the primary structure.
Combustible materials near structure - answer -The structure assessment shall
document areas next to or under a structure where combustible materials that
present a source of flame exposure might collect.
,4.2.4.1 - answer -The structure assessment shall document all vegetative fuels
and other combustible materials adjacent to and within 30 ft (9 m) of the
structure for their potential to contribute to the intensity and spread of wildland
fire.
4.2.4.2 - answer -The structure assessment shall document the presence and
location of all heat and flame sources within 30 ft (9 m) of the primary structure.
4.2.4.3 - answer -The structure assessment shall document all projections
attached to the primary structure.
4.2.4.4 - answer -The structure assessment shall document detached structures
within 30 ft (9 m) of the primary structure that might be ignited by flames, radiant
heat, or firebrands from wildland fires.
4.2.4.5 - answer -The structure assessment shall document vehicle parking areas
within 30 ft (9 m) of any surface of the structure.
4.2.5.1 - answer -The structure assessment shall document vegetation within the
area between the outer edge of the immediate landscaped area and the extent of
the structure ignition zone as potential fuel that can convey the fire to the
structure.
4.2.5.2 - answer -The structure assessment shall document the species and
location of trees and the separation of tree crowns within the area between the
outer edge of the immediate landscaped area and the extent of the structure
ignition zone.
, 4.2.5.3 - answer -The structure assessment shall document the presence and
location of all heat and flame sources within the area between the outer edge of
the immediate landscaped area and the extent of the structure ignition zone.
4.2.5.4 - answer -The structure assessment shall document detached structures
within the area between the outer edge of the immediate landscaped area and
the extent of the structure ignition zone that might be ignited by flames, radiant
heat, or firebrands from wildland fires.
4.2.5.5 - answer -The structure assessment shall document vehicle parking areas
within the area between the outer edges of the immediate landscaped area and
the extent of the structure ignition zone.
4.2.5.6 - answer -The structure assessment shall document all projections
attached to the primary structure that extend beyond the immediate landscaped
area.
4.2.5.7 - answer -The structure assessment shall document all other factors that
can affect the risk of ignition or the spread of wildland fire on improved property
within the structure ignition zone, including the risk of structure fires spreading to
vegetation.
4.2.5.8 - answer -Any structure that fails to comply with the requirements of
Chapter 5 shall be deemed to increase the risk of the spread of wildland fire to
improved property and the risk of fires on improved property spreading to
wildland fuels.
Roof Gutters - answer -Roof gutters, downspouts, and connectors shall be
noncombustible, and roof gutters shall be covered with an approved
noncombustible means to minimize the accumulation of debris.