1. For ESFR sprinklers, the clearance between sprinkler 36 inches
and the top of the storage shall be...
2. Permits required for the removal of a standpipe sys- State fire marshal
tem on state property, when not issued by the local
fire code official, shall be obtained from...
3. Components that do not affect systems perfor- True
mance such as drain piping, drain valves, and signs
shall not be required to be listed...
4. Under certain circumstances, NFPA 13 allows the use CPVC
of "other" types of pipe or tube materials including...
5. The minimum operating pressure of any sprinkler True
head in a residential (13D) sprinkler system shall
be the higher of the minimum operating pressure
specified by the listing or 7 PSI...
6. Equipment, materials, or services included in a list Listed
by an organization that us to the authority having
jurisdiction and concerned with evaluation of prod-
ucts or services, that maintains periodic inspection
of production of listed equipment or materials or
periodic evaluation of services, and whose listing
states the either the equipment, materials, or ser-
vices meets the appropriate designated standards
or has been tested and found suitable for a specified
purpose is a definition of...
7. Panel construction and other construction were Obstructed construction
beams, trusses and other members impede heat
flow or water distribution in a in a matter that ma-
, Ohio Sprinkler Technician Practice Test
terially affects the ability of sprinklers to control or
suppress fire is know as...
8. Ordinary hazard (groupI) occupancies have low com- False
bustibility, moderate amounts of combustibles may
exceed 12 feet...
9. A valve or device designed for the purpose of reduc- Pressure regulating valve
ing downstream under flowing (residual) conditions
only is a...
10. For large drop sprinkler the maximum distance from Not exceeding one half of the
the sprinkler to the wall shall be... allowable distance between
sprinklers
11. For extended coverage sidewall spray sprinklers, the Ceilings and roofs
deflection of sprinklers shall be aligned to...
12. For stages greater than 1,000 square feet in area, 3
they shall be equipped with a class... standpipe sys-
tem with 1.5 inch and 2.5 inch hose connections on
each side of the stage.
13. In the NFPA 13D standard, sprinklers shall not be True
required in the bathrooms of 55 square feet or less...
14. Manual standpipe systems shall not be used in True
high-rise buildings...
15. All fire department connections shall be supplied Listed check valve near the
with... point where it joins the system
16. Dry standpipes shall only be used where piping is True
subject to freezing...