NYC Master Electrician Licensing Examination
2026/2027 | NYC Department of Buildings |
Verified Questions & Answers | 100% Correct
Solutions
Q: Type ____ is multiconductor cable identified for use as underground service entrance
cable.
Answer
Type USE cable
Q: Knife switch rated for more than 1200 Amps at 250Volts or less
Answer
Can be used only as isolating switch, shall not be opened under load
Q: Track lighting with outlets in a bathroom is not allowed because ?
Answer
Track lighting has receptacle
Q: Where internal combustion engines are used as the prime motor, an on site fuel supply
shall be provided with an on premise fuel supply sufficient for not less than ____ hours full
demand operation of the system
Answer
6 hours
,https://www.stuvia.com/user/quizbit07
Q: Fixed in place X-ray equipment properly supplied by a branch circuit rated at not over
____ amperes shall be permitted to be supplied through a suitable attachment plug cap and
hard service cable cord.
Answer
30 Amps
Q: Where skin effect exist the ferromagnetic envelope shall be bonded at ____.
Answer
Both ends
Q: GFCI protection at a carnival is not required for equipment at circuit if the receptacle is of
the ____type.
Answer
Locking
Q: The maximum voltage drop from service point to the last over-current device in a dwelling
unit?
Answer
4%
Q: Which of the following statements best describe the grounding requirement for central
vacuum outlet
Answer
Accessible non current carrying metal parts are required to be connected to an equipment
grounding conductor.
,https://www.stuvia.com/user/quizbit07
Q: In healthcare facilities, patient bed receptacles located in general care areas shall be
supplied by at least two branch circuits, which ____permitted to originate from two separate
transfer switches on the emergency system
Answer
Are permitted
Q: Patient care areas of healthcare facilities ____ areas such as business offices, corridors,
lounges ,day rooms, or similar areas
Answer
Do not include
Q: The patient care area is any portion of the healthcare facility where patients are intended to
be ____or ____.
Answer
Examined or treated
Q: Each general care area patient bed location in a healthcare facility must be provided with
four ____ or ____ duplex receptacles
Answer
Single or two
, https://www.stuvia.com/user/quizbit07
Q: A hospital is a building or portion thereof used for medical, psychiatric,obstetrical , or
surgical, care on a 24 hour basis of ____ or more patients
Answer
Four
Q: Where installed to reduce electrical noise for electronic equipment, electrical continuity of
the metal raceways shall not be required and metal raceway can terminate a (an) ____
nonmetallic fitting or spacer on electronic equipment
Answer
Listed fitting
Q: Feeder and branch circuit conductors within ____ inches of a Ballast shall have an
insulation temperature rating not lower than 90°C (194°F) unless supplying a luminaiere
marked as suitable for a different insulation temperature
Answer
3 inches
Q: Manufactured wiring systems constructed with type MC cable shall be supported and
secured at intervals not exceeding ____ ft.
Answer
6 ft
Q: Where a main bonding jumper or a system bonding jumper is a screw only the screw shall
be identified with a ____ that shall be visible with the screw installed
Answer