Indoor manifold rooms must be separated by ______ fire rated walls and floors with a
______ opening.
A 1 hour, 1 hour
B 2 hour, 1 hour
C 1 hour, 3/4 hour
D No wall fire rating is required - ANSWERS-1 hour, 3/4 hour
Per ASSE 6000 Annex D, the medical air compressor intake location and filter condition
should be checked _______________.
A Daily
B Weekly
C Quarterly
D Annually - ANSWERS-Quarterly
Minimum Maintenance Schedule, per ASSE 6000 Annex D, should include annual
checking of ________________ for Flow, Pressure/Vacuum, Damage, and Wear.
A All outlets & inlets
B All critical care outlets & inlets
C 50% of all critical care outlets
,D Annual testing of outlets & inlets is not recommended - ANSWERS-All critical care
outlets & inlets
A medical gas systems utilizing ___________ for patient care shall be considered
Category 1 since failure of such equipment is likely to cause major injury or death to
patients or caregivers.
A Ventilator
B Anesthesia machine with a ventilator
C either A or B
D Neither A nor B - ANSWERS-either A or B
Category 1 requirements apply where procedures involving _____________ are
performed.
A Deep Sedation or General Anesthesia
B Mild sedation
C Moderate sedation
D Mild or Moderate Sedation - ANSWERS-Deep Sedation or General Anesthesia
At sea level the atmospheric pressure is 14.7 psia. What is the absolute pressure of a
50 psig (gauge pressure) system at sea level?
A 64.7 psia
B 50 psia
C 34.7 psia
D 60 psia - ANSWERS-64.7 psia
Medical gas cylinders and flammable gases may be stored in the same enclosure
A TRUE
B FALSE - ANSWERS-FALSE
Medical gas cylinders must be prevented from reaching temperatures above ______ oF
A 75
, B 100
C 125
D 200 - ANSWERS-125
___________________ source supply manifolds shall be prevented from reaching
temperatures lower than manufacturers recommendations but never lower than 20oF
A Nitrous Oxide
B Carbon Dioxide
C Nitrous Oxide & Carbon Dioxide
D There is no minimum temperature limit - ANSWERS-Nitrous Oxide & Carbon Dioxide
The entrance to indoor locations containing positive pressure gases other than oxygen
and medical air shall be labeled including: ______________
A Positive Pressure Gases
B No Smoking or Open Flame
C Room May Have Insufficient Oxygen - Open Door and Allow Room to Ventilate
Before Entering
D All of the above - ANSWERS-All of the above
If heat is necessary to keep an indoor manifold enclosure above 20oF and the
manufacturer's recommended minimum ambient temperature it may be provided by:
A Any in-room electric heating element
B In-room heating element with a maximum temperature of 266oF
C Fuel fired equipment in the room
D Heat blanket with maximum temperature of 300oF - ANSWERS-In-room heating
element with a maximum temperature of 266oF
Two entries/exits are required for ___________________ gas supplies.
A Outdoor Cryogenic Gas Supplies only
B Outdoor Cylinder Gas Supplies in an enclosure >200ft2 only