QUESTIONS AND CORRECT ANSWERS|
A+ GRADE VERIFIED ANSWERS
In the event of a fire at a bulk storage plant, what actions
would you direct to extinguish the fire? Correct Answer
Use the fire hose to keep the container contents as cool
as possible and get to leak source and cut off the gas flow
What type of vent pipe shall be installed on a LP Gas wall
furnace in excess of 50,000 BTU? Correct Answer Type B
Industrial trucks (forklift, etc.) with permanently mounted
fuel tanks must be refueled at what location? Correct
Answer Outside the building
At what distance is the legal minimum between the point
of transfer of LP Gas and an outdoor place of public
assembly, such as school yards, athletic fields,
playgrounds, etc.? Correct Answer 50 ft.
At what distance is the legal minimum between the point
of transfer of LP Gas and a building with fire resistant
walls? Correct Answer 10 ft.
What is the minimum distance required between the relief
valve on an ASME container of 125 water gallons or less
,capacity and a building opening below the level of the
relief valve discharge? Correct Answer 5 ft.
What is the minimum distance between the point of
transfer of LP Gas and the centerline of the nearest
mainline railroad track? Correct Answer 25 ft.
In case of regulators installed in buildings and vented to
the outside, the discharge outlet must be what distance
horizontally away or below a building opening? Correct
Answer 3 ft.
What is the maximum length of a flexible component
connector used in a bulk plant piping system to prevent
damage from containers settling? Correct Answer 36
inches
What method would re-supply a permanent customer fuel
storage facility that is located on a roof top? Correct
Answer Use a freight elevator off limits to the public to
transport cylinder
A liquid transfer hose equipped with a shutoff valve at the
discharge end shall have what installed in the line?
Correct Answer A hydrostatic relief valve
All transfer hoses used to fill individual containers indoors
shall not exceed what inside diameters (I.D.)? Correct
Answer 1/2 inch I.D.
, All bulk storage plants shall be enclosed within a minimum
six foot high industrial type fence or otherwise adequately
protected by what method? Correct Answer Provide
properly trained guard personnel at the facility
Hoses that are used on the lo pressure side of a regulator
to connect to other than domestic and commercial
appliances shall not exceed what length? Correct Answer
72 inches
In your work you will be installing heaters, cookstoves,
etc., in mobile homes and recreational vehicles. In making
a decision to install such an appliance, what type of
approval would you look for before making the
installation? Correct Answer Approval for such service by
the American Gas Association
DOT cylinders and/or containers for LP Gas shall be
requalified according to DOT regulations, who is
responsible got ensuring that these cylinders and/or
containers are requalified? Correct Answer The person
filling the cylinder and/or container
When a dealer takes over another dealer's account, what
action is NOT a legal requirement of the new gas
supplier? Correct Answer Ensure that all financial
obligations to the previous dealer have been satisfied
Bulk storage plants that have a minimum six foot high
industrial type fence to protect against tampering and
trespassing must have a minimum of what means for