If you have (2) parallel 300 KCMIL conductors installed in separate runs of PVC, what
size EGC is needed in each pipe? - ANSWER-#1 If you have (2) sets of 3-phase 250
KCMIL conductors in separate
dividers of cable tray for a service, what size EGC is needed? -
ANSWER-4/0
A singles phase 325 amp load is supplied by a 350 amp breaker. The conductors are 400
KCMIL with a #3 EGC. If the supply conductors are
increased to 500 KCMIL, what would be the new size EGC? -
ANSWER-#2
What is the min size copper-clad grounding electrode conductor needed for a 200amp single
phase dwelling copper feeder - ANSWER-2 awg
The min distance any edge of a stud must be from the edge of a hole for nm cable is? -
ANSWER-1 1/4 in
,2 | Page
Direct burial cable shall be installed how many inches below streets and parking lots?
- ANSWER-24
When direct burial exits the ground, it shall be enclosed in a raceway or
enclosure extending to a level of ____ ft above grade? -
ANSWER-8
At what rated voltage does direct burial cable have to be shielded? -
ANSWER-2000 volts
What is the max distance for within sight? - SOLUTION=50 ft
An electrical device that consists of a frame, a lunger and uses an up and down motion to
operate is called what? - SOLUTION=Solenoid
What are the types of equipment grounding conductors? - SOLUTION=rigid metal conduit
and electrical metal tubing A restaurant has a 15.5 foot pug strip for all their television
systems which are likely to be used at the same time. What is the VA? - SOLUTION=2880
VA
An apartment has 8 water heaters a 800 watts, what is the VA? -
SOLUTION=4800
A commercial garage has 55ft of track lighting, what is the VA?
- SOLUTION=4200
, 3 | Page
240 volt to ground, 200 amp panel in condition 3 needs a minimum front clearance of ___ft?
- SOLUTION=4
What is the minimum clearance in front of a service panel? -
SOLUTION=3ft
The width of the 120/240 volt panel working area shall be a minimum of __ft, and the door
shall be open able to at least 90deg - SOLUTION=2 1/2
Manhole covers shall weigh more than how many pounds? -
SOLUTION=100lbs
a 240-volt boat hoist receptacle has to be? - SOLUTION=GFCI Protected
Non-dwelling unit receptacles installed in/on the __ shall be
GFCI protected and installed in a readily accessible location - SOLUTION=roof tops and
outdoors
Rooftop units being supplied by feeder panels shall have a receptacle that is ___? -
SOLUTION=GFCI
What is the minimum rating for a laundry circuit in a single family dwelling? - SOLUTION=20
amps 1500 watts
Branch circuits in hotels and assisted living units have to be? -
SOLUTION=AFCi