CMASCO1 Exam questions and answers Graded A+| 2026 Updated Feature 1C -Engine Start Time Delay — Prevents unnecessary generator starts during momentary outages; if normal returns before delay expires, no start. If delay expires, NR relay starts the generator. Default 3 s; range 0-6 s; extended to 0-60:59 with accessories. Feature 1F -Generator Stabilization Time Delay — Allows generator V/F to stabilize before transfer to emergency. Default 4 s; adjustable 0-6 s. Feature 2B -Transfer to Emergency Time Delay — Staggers loads to avoid block loading; starts once emergency is accepted. Normal failure and test delays independently adjustable 0-60:59; default 0 s. Feature 2E -Engine Cooldown Time Delay — Keeps generator running unloaded after retransfer to normal; on expiry, shutdown. Default 5 min; range 0-60:59. Feature 3A -Retransfer to Normal Time Delay — Ensures utility is stable before switching back; starts when normal acceptable; resets on any instability. Normal failure 0-60:59; Test 0-9:59:59; de