NEWEST ACTUAL EXAM COMPLETE QUESTIONS AND
CORRECT DETAILED ANSWERS (VERIFIED ANSWERS)
|ALREADY GRADED A+||BRAND NEW!! 2026-2027
The interior of enclosures or raceways installed underground
shall be considered to be a _.
wet location
In guest rooms or guest suites of hotels and motels, and sleeping
rooms in dormitories, at LEAST _____ general purpose receptacle(s)
installed in the room is/are required to be readily accessible.
two
Determine the ampacity of a size 1/0 AWG THW copper current-
carrying conductor installed in a common raceway with three (3)
other current-
carrying conductors of the same size. Ambient temperature is 86°F.
120 amperes
,A plate-type grounding electrode shall be installed below the
surface of the earth NOT less than _.
30 inches
In Class II, Division 1, hazardous locations, where pendant mounted
luminaires are suspended by rigid metal conduit (RMC) and a
means for flexibility is not provided, the RMC stem shall have a
length of NOT more than _.
12 inches
For the purpose of calculating the general lighting load for a
dwelling unit, the floor area should include all of the following
EXCEPT ______________________________________________ _.
an open porch not adaptable for future use
Determine the MINIMUM trade size electrical metallic tubing (EMT)
required to enclose eight (8) size 6 AWG copper conductors with
THHW insulation, where installed in a 60 foot conduit run.
1 1/4
,For the purpose of determining conductor fill in a device box, a
single-pole switch is counted as equal to _____ conductor(s), based
on the largest
conductor connected to the switch.
two
What is the MINIMUM size equipment grounding conductor
required by the NEC® for a branch circuit protected by a 50-
ampere rated circuit breaker?
10 AWG
What is the MINIMUM size equipment grounding conductor
required by the NEC® for a branch circuit protected by a 50-
ampere rated circuit breaker?
15 amperes
When determining the required ampacity of the branch-circuit
conductors to supply an AC, three-phase, continuous-duty motor,
current values of the motor given on _____ shall be used.
Table 430.250 of the NEC®
, The short-circuit and ground-fault protective device protecting an
air-
conditioner motor-compressor branch-circuit shall have sufficient to
permit the motor-compressor and other motors to start and
accelerate their loads.
time delay
In a health care facility, low-voltage electrical equipment that is
likely to become energized and is frequently in contact with the
bodies of patients shall operate on a voltage of _____ volts or less if
the equipment is not
approved as intrinsically safe, double-insulated, or moisture-resistant.
10
Before demand factors are taken into consideration for commercial
buildings, general purpose receptacle loads are to be computed at
NOT less than _____ VA per single or duplex receptacle mounted on
one yoke.
180
Where an exposed outlet box is installed under metal-
corrugated roof decking, a clearance of NOT less than _____ is to
be maintained from the lowest surface of the roof decking to
the top of the box.
1 1/2 inches