1. The hydrostatic test interval for a dry chemical extinguisher with a
stainless steel shell is every __ years - correct answer - 5
2. The hydrostatic test interval for a stored-pressure water, water mist,
loaded stream, and/or antifreeze is __ years - correct answer - 5
3. The hydrostatic test interval for a Wetting agent extinguisher is __ years.
- correct answer - 5
4. The Hydrostatic test interval for a AFFF (aqueous film-forming foam)
extinguisher is __ years. - correct answer - 5
5. The Hydrostatic test interval for a FFFP (film-forming fluoroprotein foam)
extinguisher is __ years. - correct answer - 5
, Page |2
6. The hydrostatic test interval for a Carbon Dioxide extinguisher is __
years. - correct answer - 5
7. The hydrostatic test interval for a Wet Chemical extinguisher is __ years.
- correct answer - 5
8. The hydrostatic test interval for a Dry chemical, stored-pressure, with
mild steel shells, brazed brass shells, or aluminum shells is __ years. -
correct answer - 12
9. The hydrostatic test interval for a Dry chemical, cartridge- or cylinder-
operated, with mild steel shells is __ years. - correct answer - 12
10. The hydrostatic test interval for a Halogenated Agent extinguisher is
__ years. - correct answer - 12
11. The hydrostatic test interval for a Dry powder, stored-pressure,
cartridge- or cylinder- operated, with mild steel shells extinguisher is __
years. - correct answer - 12
12. The maintenance internal examination for a stored-pressure loaded
stream and antifreeze is __ years. - correct answer - 1