S-12 CITYWIDE SPRINKLER
SYSTEMS, S12 sprinkler test Questions
with Detailed Verified Answers
Question: THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS.
AND TO DETERMINE QUALIFICATIONS.
Ans: OWNER
Question: RECORDS OF ALL INSPECTIONS AND MX SHALL BE
MAINTAINED ON PREMISES FOR A MIN. OF __________ YEARS.
Ans: 3
Question: THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO
COMPLY WITH REQUIREMENTS.
Ans: IMPAIRMENT COORDINATOR
Question: REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE
THAN ________ FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM
SERVICE.
Ans: 1
, Page | 2
Question: SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S)
ARE CONSIDERED UNPLANNED OUT OF SERVICE CONDITIONS.
Ans: 1
Question: NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM
IS RETURNED TO SERVICE WITHIN ______ HOURS.
Ans: 8
Question: FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER
SHALL IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE
FIRE DEPT.
Ans: OWNER OF THE BUILDING
Question: IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED
WITHIN _________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT.
Ans: 30
Question: WHAT DOES "OOS" STAND FOR?
Ans: OUT OF SERVICE
Question: OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT
FIRE DEPT. CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND
CENTER
, Page | 3
Ans: TAGS
Question: A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN
CONTROL VALVE AND ANY SECTIONAL VALVES.
Ans: MASTER FIRE SUPPRESSION PIPING CONTRACTOR
Question: __________ SHALL BE POSTED ON THE TAG INDICATING BOTH
STATIC AND FLOW PRESSURES BEFORE AND AFTER.
Ans: DRAIN TEST RESULTS
Question: GREEN TAGS INDICATE THAT __________.
Ans: NO IMPAIRMENT WAS FOUND
Question: GREEN TAGS WILL BE PLACED ON THE ____________.
Ans: MAIN CONTROL VALVE
Question: SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE
A ____________ TAG PLACED ON THE MAIN CONTROL VALVE.
Ans: RED
Question: A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON
CONNECTIONS TO INDICATE THE SYSTEM IS FULLY OUT OF SERVICE.
, Page | 4
Ans: WHITE
Question: A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON
CONNECTIONS TO INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE.
Ans: BLUE
Question: THE IMPAIRMENT COORDINATOR WILL NOTIFY THE
___________ CARRIER, CENTRAL STATION AND OCCUPANTS.
Ans: INSURANCE
Question: PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________
SHALL ENSURE THAT NECESSARY TESTS AND INSPECTIONS ARE
CONDUCTED.
Ans: IMPAIRMENT COORDINATOR
Question: GLYCERIN NOT GREATER THAN _________ PERCENT OR
GLYCOL NOT GREATHER THAN ________ PERCENT SHALL BE USED TO
PROTECT FROM FREEZING.
Ans: 50, 40
Question: THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE
POSTED NEAR THE ____________.
Ans: MAIN CONTROL VALVE